Background

The customer at a drinking water treatment plant sought to replace their outdated centrifuge dewatering technology. Through a pilot test conducted at a drinking water treatment plant in France, the suitability of the VOLUTE DUO™ dewatering technology for the customer’s sludge was evaluated.

Installation details

During the pilot test, the VOLUTE DUO™ RVP-241 demonstrated excellent performance, achieving a dryness of up to 27% (average 24-25% DSC) for the produced cake. The unit was capable of processing a throughput of 15-25 kg-DS/h. Filtrate quality was excellent, with a capture rate exceeding 99%.

Considering the high inorganic content of the sludge (>70%), VOLUTE DUO™ stands out as the most suitable long-term replacement for the existing centrifuge dewatering technology. Its two advantages – low risk of blockage and reduced OPEX and maintenance costs make it a favorable option for the customer.

Wastewater treatment plant conditions and performance data

Model: RVP-241
Sludge type: WAS
Total solids: 6.12 %
Inorganic content: 74 %
Flow rate: 0.35 m3/h
DS throughput: 21.4 kg-DS/h
Cake solids content: 26.7 %
Capture rate: 99.2 %